EX9018BL-M - Modbus RTU 8 thermocouple input with break-line detection
EX9018BL-M Modbus RTU an. In 16 bit I/O for thermocouple. Measures voltage / current / temperature with J, K, T, E, R, S, B or N sensors. Break-line detection
Opis
The EX9018BL-M Analog In 16 bit Modbus RTU module for thermocouple excels at use for temperature measurement with one of the sensors J, K, T, E, R, S, B or N or may be used to measure analogue voltages in the measuring ranges ±15mV, ±50mV, ±100mV, ±500mV, ±1V and ±2,5V or currents between ±20mA with a sampling rate of 10 Hz. The Analog In RS485 module has open-loop detection and can be operated in a wide temperature range.
Features:
- measure voltages in measuring ranges from ±15mV to ±2,5V
- support all popular thermocouple
- break-line detection
- output as RS485 interface
- Communicate via Modbus-RTU
- In- and Output galvanically isolated
- manual configuration or with supplied software
- power supply 10 - 30VDC
Funkcje
Interfejs |
|
---|---|
Komunikacja | RS485 |
Szybkość | 1200 - 115200 bps |
Złącze | Terminal Block |
Protokół | Modbus RTU |
Wejście/wyjście |
|
Typ | Thermocouple |
Kanały w | 8 |
Izolacji | Yes |
Wejście analogowe |
|
Kanały | 8 differential |
Rozdzielczość | 16 bit |
Całkowita częstotliwość próbkowania | 15.7 Hz |
Zakres napięć | ± 15 mV ± 50 mV ± 100 mV ± 500 mV ± 1 V ± 2.5 V |
Impedancja napięcia | 20 Mohm |
Zakres prądu | ± 20 mA |
Impedancja prądu | 125 Ohm |
Dokładność | ± 0.1 % |
Zero dryfu | ± 0.5 µV/°C |
Dryf rozpiętości | ± 25 ppm/°C |
Typ czujnika | J, K, T, E, R, S, B, N |
Funkcje |
|
Napięcie izolacji | 3000 V |
Dodatki | Thermocouple break line detection |
System |
|
Moc max. | 1 W |
Wejście zasilania | 10~30V DC |
Obudowa |
|
Kontynuuj | Din Rail Mounting |
Wymiary | 100 x 70 x 25mm |
Waga | 110g |
Środowisko |
|
Temperatura | -25~75°C |
Temperatura przechowywania | -30~75°C |
Certyfikacji | CE / FCC / WEEE / RoHS |
Inne |
|
dołączone do dostawy | Din Rail Mounting Kit |